§3.1 — Dead Loads §3.1

Definition and Scope

Dead loads consist of the weight of all materials of construction incorporated into the building including, but not limited to, walls, floors, roofs, ceilings, stairways, built-in partitions, finishes, cladding, and other similarly incorporated architectural and structural items, and fixed service equipment including the weight of cranes.

Table C3-1 — Minimum Densities for Design Loads App. C, Table C3-1
Material Density (kN/m³) Density (pcf) Category Notes
Normal-weight Concrete (NWC)23.56150ConcreteIncludes reinforcement allowance
Lightweight Concrete 110 pcf17.27110ConcreteStructural LWC
Lightweight Concrete 100 pcf15.71100ConcreteStructural LWC
Steel77.01490Metal—
Aluminum26.60169Metal—
Brick (solid, clay)18.85120Masonry—
CMU Block (normal-weight)17.27110Masonry—
Timber — Douglas Fir5.6536Timber—
Timber — Southern Pine6.2840Timber—
Granite / Marble26.38168Stone—
Soil (dry sand/gravel)15.71100Soil§3.2 lateral earth
Soil (saturated)18.85120Soil§3.2 lateral earth
Table 3.1-1 — Minimum Design Dead Loads (Area Loads) §3.1, Table 3.1-1
Component Load (kN/m²) Load (psf) Category
Ceramic / Quarry Tile 25 mm0.5311.0Floor Finish
Ceramic Tile 13 mm0.275.5Floor Finish
Hardwood Flooring 25 mm0.142.8Floor Finish
Carpet + pad0.051.0Floor Finish
Mortar Bed 25 mm0.5712.0Floor Finish
Gypsum Board 16 mm (1 layer)0.245.0Ceiling
Acoustic Tile (suspended)0.102.0Ceiling
Built-up Roofing (BUR)0.357.0Roofing
Concrete Roof Tile0.7716.0Roofing
Gravel Ballast 25 mm0.439.0Roofing
Metal Deck (corrugated steel)0.143.0Roofing
§3.2 — Forces Due to Soil and Hydrostatic Pressure §3.2

Lateral Earth Pressure (H load)

In addition to the dead loads listed in §3.1, structures below grade must be designed for the lateral pressure of adjoining soil. Per §3.2, soil loads and hydrostatic pressure are classified as H loads in ASCE 7-16 §1.2.2 and enter load combinations per §2.3.1 and §2.4.1.